Continuous Standby Power Rating Models:
15kW 60 Hz 04721 (15kW/Single Phase NG or LPV)
04722 (15kW/Single Phase NG or LPV) 20kW 60 Hz
04723 (20kW/Single Phase NG or LPV)
04724 (20kW/Single Phase NG or LPV) UL 2200 Listed
2 Year Limited Warranty
Power Matched Naturally Aspirated Generac 100 Amp Automatic Transfer Switch (UL Listed) Included with Models 04721 04723. Available for models 04722 & 04724 - 2 Year Limited Warranty.

![]()
![]()

| Model | 04721 | 04723 |
| Rated Power (kW)* | 15 | 20 |
| 60 Hz Phase | Single | Single |
| Voltage | 120/240V | 120/240V |
| Amps @ 120/240V, Single Phase 60 Hz | 125/62.5 | 166.6/83.3 |
| Engine / Alternator RPM | 1800 | 3600 |
| Engine | 1.5L OHC 4 cyl. | 1.5L OHC 4 cyl. |
| Fuel | Natural gas or LP gas | Natural gas or LP gas |
| UL 2200 Listed | Yes | Yes |
| CSA Listed | Yes | Yes |
| Main Line Circuit Breaker | 70 Amp | 90 Amp |
| Engine Cooling | Liquid | Liquid |
| Dimensions (L" x W" x H") | 68 x 30 x 40 | 68 x 30 x 40 |
| Unit Wt. (lbs.)** | 980 | 985 |
| Start/Stop Control | Cyclic cranking: 7 seconds on, 7 seconds rest. 90 seconds overcrank protection. |
| Automatic Low Oil Shutdown | Standard |
| Overspeed Shutdown | Standard, 70 Hz |
| Overcrank Protection | Standard |
| Automatic Voltage Regulator with Over-Voltage Protection | Standard |
| Engine Warmup | 15 seconds |
| Engine Cool-Down | 1 minute |
| Safety Fuse | Standard |
| Safety Fuse | Standard |
| Starter Lockout | Starter cannot re-engage until 5 seconds after engine has stopped |
| 2 Amp Timed Trickle Battery Charger | Standard |
| Auto Switch | Utility failure/7 day exercise |
| Off Switch | Stops unit. Power is removed. Control and charger still operate |
| Manual / Test | Start with starter control, unit stays on. If utility fails, transfer to load takes place |
** Includes Transfer Switch
| INNOVATIVE DESIGN & PROTOTYPE TESTING are key components of GENERAC’S success in “IMPROVING POWER BY DESIGN.” But it doesn’t stop there. Total commitment to component testing, reliability testing, environmental testing, destruction and life testing, plus testing to applicable CSA, NEMA, EGSA, and other standards, allows you to choose GENERAC POWER SYSTEMS with the confidence that these systems will provide superior performance. - TEST CRITERIA: - PROTOTYPE TESTED - SYSTEM TORSIONAL TESTED - ELECTRO-MAGNETIC INTERFERENCE - NEMA MG1-22 EVALUATION - MOTOR STARTING ABILITY |
SOLID-STATE, FREQUENCY COMPENSATED VOLTAGE REGULATION. This state-of-the-art power maximizing regulation system is standard on all Generac models. It provides optimized FAST RESPONSE to changing load conditions and MAXIMUM MOTOR STARTING CAPABILITY by electronically torque-matching the surge loads to the engine. - SINGLE SOURCE SERVICE RESPONSE from Generac’s dealer network provides parts and service know-how for the entire unit, from the engine to the smallest electronic component. You are never on your own when you own a GENERAC POWER SYSTEM. - GENERAC TRANSFER SWITCHES. Long life and reliability are synonymous with GENERAC POWER SYSTEMS. One reason for this confidence is that the GENERAC product line includes its own transfer systems and controls for total system compatibility.
|
APPLICATION & ENGINEERING DATA Home Standby - 20 Home Standby 15
| GENERATOR SPECIFICATIONS TYPE Home Standby 15 .......................................... Four-pole, revolving field TYPE Home Standby 20 ........................................... Two-pole, revolving field ROTOR INSULATION ....................................................................... Class F STATOR INSULATION ...................................................................... Class F VOLTAGE WAVE FORM DEVIATION .................................................... <5% TOTAL HARMONIC DISTORTION (line to line) .................................... <5% TELEPHONE INTERFERENCE FACTOR (TIF) ..................................... <50 ALTERNATOR ................................................. Self-ventilated and drip-proof BEARINGS (PRE-LUBED & SEALED) ....................................................... 1 COUPLING .................................................................... Direct, Flexible Disc LOAD CAPACITY (STANDBY) ............................................................. 100% NOTE: Emergency loading in compliance with NFPA 99, NFPA 110, paragraph 5-13.2.6. Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349, ISO3046, and DIN6271 standards. EXCITATION SYSTEM DIRECT .................................................................. DC excitation system Low-velocity brushes and slip rings REGULATION ......................................................................... Solid-state ±1% regulation GENERATOR FEATURES > Two/Four pole, revolving field generator, directly connected to the engine shaft through a heavy-duty, flexible disc for permanent alignment. > Generator meets temperature rise standards for class “F” insulation as defined by NEMA MG1-22. > Stator windings are “trickle” varnished and rotor windings are “roll-dipped” for complete impregnation. > Unit tested for motorstarting ability by measuring instantaneous voltage dip with a waveform data acquisition system. All models utilize an advanced wire harness design for reliable interconnection within the circuitry. > Magnetic circuit, including amortisseur windings, tooth and skewed stator design, provides a minimal level of waveform distortion and an electromagnetic interference level which meets accepted requirements for standard AM radio, TV, and marine radio telephone applications. >Voltage waveform deviation, total harmonic content of the AC waveform, and balanced T.I.F. (Telephone Influence Factor) have been evaluated to acceptable standards in accordance with NEMA MG1-22. > Alternator is of drip-proof guarded construction. > Fully life-tested protective systems, including “field circuit and thermal overload protection” and standard mainline circuit breakers capable of handling full output capacity. > System torsional acceptability confirmed during prototype testing.
| ENGINE SPECIFICATIONS MAKE .......................................................................................... GENERAC MODEL ....................................................................................... MMC 4G15 CYLINDERS ..................................................................................... 4 in-line DISPLACEMENT ........................................................ 1.5 Liter (91.5 cu. in.) BORE ............................................................................... 75.5 mm (2.97 in.) STROKE ............................................................................. 82 mm (3.23 in.) COMPRESSION RATIO ........................................................................ 9:4:1 INTAKE AIR ................................................................... Naturally Aspirated NUMBER OF MAIN BEARINGS ................................................................ 5 CONNECTING RODS .................................................... 4-Drop forged steel CYLINDER HEAD ........................................................................... S.O.H.C. PISTONS .......................................................................... 4-Aluminum Alloy CRANKSHAFT ................................................................ Drop Forged Steel VALVE TRAIN LIFTER TYPE .................................................................... Rocker Arm Type INTAKE VALVE MATERIAL ......................... High Temperature Alloy Forged EXHAUST VALVE MATERIAL ..................... High Temperature Alloy Forged VALVE SEATS ........................................................................... Replaceable ENGINE GOVERNOR ELECTRONIC.............................................................................. Standard FREQUENCY REGULATION, NO-LOAD TO FULL LOAD ............ 0.5% STEADY STATE REGULATION .................................................. ±0.25% LUBRICATION SYSTEM TYPE OF OIL PUMP ............................................................................ Gear OIL FILTER ...................................................................... Full flow, cartridge CRANKCASE CAPACITY .................................................. 3.8 Liters (4 qts.) COOLING SYSTEM TYPE OF SYSTEM ........................................ Pressurized, closed recovery WATER PUMP .......................................................... Pre-lubed, self-sealing TYPE OF FAN ................................................................................... Pusher NUMBER OF FAN BLADES ....................................................................... 6 DIAMETER OF FAN ......................................................... 380 mm (15.0 in.) COOLANT HEATER ........................................................................... 500 W FUEL SYSTEM FUEL Natural Gas or L.P. Vapor .......................................................... Standard CARBURETOR ............................................................................ Down draft SECONDARY FUEL REGULATOR. Nat. Gas or L.P. Vapor Systems AUTOMATIC FUEL LOCKOFF SOLENOID ................................... Standard OPERATING FUEL PRESSURE VAPOR SYSTEMS ..Nat. Gas 5 to 14” H2O LP Vapor.....11” to 14” H2O ELECTRICAL SYSTEM BATTERY CHARGE ALTERNATOR ................................... 15 Amps at 12 V STARTER MOTOR .................................................................................. 12 V RECOMMENDED BATTERY ............... 12 V, 525 CCA @ 0o F/75 A.H., 26R GROUND POLARITY ..................................................................... Negative
|
Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc.
| STANDBY | ||||||||||||||||
|
Home Standby-15 |
Home Standby-20 | |||||||||||||||
|
Rated | Rated | |||||||||||||||
| GENERATOR OUTPUT VOLTAGE/KW - 60Hz 120/240V, 1-phase, 1.0 pf |
N.G./L.P. |
AMP |
N.G./L.P. |
AMP | ||||||||||||
|
15 |
62.5 |
20 |
83.3 | |||||||||||||
|
MOTORSTARTING | ||||||||||||||||
| Maximum at 35% instantaneous voltage dip | ||||||||||||||||
| with standard alternator; 60 Hz |
28 KVA |
39 KVA | ||||||||||||||
|
FUEL | N.G. |
L.P. |
N.G. |
L.P. | ||||||||||||
| ft.3 /hr.(gal./hr.) Fuel consumption - 60 Hz--100% Load |
265 |
110 (3.0) |
369 |
153 (4.2) | ||||||||||||
|
m3 /hr. |
7.5 |
3.1 |
10.4 |
4.3 | ||||||||||||
|
COOLING | ||||||||||||||||
|
Coolant capacity |
System lit.(US gal.) |
7.5 (2) |
7.5 (2) | |||||||||||||
| Engine lit.(US gal.) |
0.9 (0.25) |
0.9 (0.25) | ||||||||||||||
|
Radiator lit.(US gal.) |
6.6 (1.75) |
6.6 (1.75) | ||||||||||||||
| Coolant flow/min. | 60 Hz lit.(US gal.) |
25 (6.6) |
40 (10.6) | |||||||||||||
| Heat rejection to coolant |
60 Hz BTU/hr. |
72,000 |
96,000 | |||||||||||||
|
Cooling air flow |
60 Hz m3/min. (cfm) |
40 (883) |
45 (1590) | |||||||||||||
| COMBUSTION AIR REQUIREMENTS | ||||||||||||||||
| Flow at rated power 60 Hz m3/min. (cfm) |
1.2 (41) |
1.6 (57) | ||||||||||||||
|
EXHAUST | ||||||||||||||||
|
Exhaust flow at rated output 60 Hz m3/min. | (cfm) |
3.9 (137) |
6.0 (212) | |||||||||||||
| Max. recommended back pressure |
Kpa (Hg) |
5.0 (1.5") |
5.0 (1.5") | |||||||||||||
| Exhaust temp. at rated output |
°C (°F) |
621 (1150) |
704 (1300) | |||||||||||||
| Exhaust outlet size | N.P.T. (female) | 1.5" |
1.5" | |||||||||||||
| ENGINE | ||||||||||||||||
|
Rated at RPM |
60 Hz |
1800 |
3600 | |||||||||||||
|
HP at rated KW |
60 Hz |
24 |
32 | |||||||||||||
|
Piston speed |
60 Hz m/min. (ft./min.) |
295 (969) |
590 (1937) | |||||||||||||
| BMEP |
60 Hz |
116 |
78 | |||||||||||||
|
FOR AMBIENT CONDITIONS | ||||||||||||||||
| Temperature | ||||||||||||||||
| -1.65% for every 10°F above - °F |
77 |
77 | ||||||||||||||
|
Altitude | ||||||||||||||||
| -3% for every 1000 ft. above - ft. |
600 |
600 | ||||||||||||||
|
SOUND OUTPUT | ||||||||||||||||
| In dB(A) at 23 feet with generator operating at full load |
75 |
81 | ||||||||||||||
|
TRANSFER SWITCH SPECIFICATIONS (If so equipped) |
| |||||||||||||||
|
No. of Poles |
2 | |||||||||||||||
|
Current Rating (amps) |
100 | |||||||||||||||
|
Voltage Rating (VAC) |
250 | |||||||||||||||
|
Utility Voltage Monitor (fixed) |
| |||||||||||||||
|
Pick-up |
80% | |||||||||||||||
|
Enclosure - NEMA 3R |
Standard | |||||||||||||||
|
Dropout |
60% | |||||||||||||||
|
Return to Utility |
1 minute | |||||||||||||||
|
Exerciser 15 minutes weekly |
Standard | |||||||||||||||
|
UL Listed |
Standard | |||||||||||||||
|
Dimensions (H" x W" x D") |
20 x 15 x 7 | |||||||||||||||
| Weight |
35 lbs. | |||||||||||||||
STANDARD ENGINE & SAFETY FEATURES
Home Standby - 15 Home Standby - 20 High Coolant Temperature Automatic Shutdown Battery Charge Alternator Low Coolant Level Automatic Shutdown Battery Cables Low Oil Pressure Automatic Shutdown Battery Tray Overspeed Automatic Shutdown (Solid-state) Vibration Isolation of Unit to Mounting Base Crank Limiter (Solid-state) 12 Volt, Solenoid-Activated Starter Motor Oil Drain Extension Air Cleaner Radiator Drain Extension Fan Guard Factory-Installed Cool Flow Radiator Control Console Closed Coolant Recovery System UV/Ozone Resistant Hoses Stainless Steel Flexible Exhaust Connection Battery Trickle Charger Rubber-Booted Engine Electrical Connections Flexible Fuel Line Fuel Lockoff Solenoid Critical Exhaust Silencer Isochronous Governor Main Line Circuit Breaker Secondary Fuel Regulator (N.G. and L.P.) Automatic Transfer Switch Weather Protective Enclosure (Locking Type) (Included with models 04721 & 04723 only)
|
Battery Charge Alternator Battery Cables Battery Tray Vibration Isolation of Unit to Mounting Base 12 Volt, Solenoid-Activated Starter Motor Air Cleaner Fan Guard Control Console UV/Ozone Resistant Hoses Battery Trickle Charger Flexible Fuel Line Critical Exhaust Silencer Main Line Circuit Breaker Automatic Transfer Switch (Included with models 04721 & 04723 only)
|


Portable Generators | Standby Generators | Air Compressors | UPS Uninterruptible Power Sources | Automotive Parts
Call Toll Free 1-800-931-0552 - Out of Country: 720-322-0500